Warranty Card
- 108 -
1016H Device
code
The set value is the percentage of the relative value, 10000 corresponds to
100.00%, -10000 corresponds to -100.00%.
For frequency dimension data,it is the percentage of the maximum output
frequency (F0.08) ; for torque dimension data, the percentage is F5.07 (torque upper
limit digital setting) .
Control command is input to the inverter: (write only)
Command word address
Command function
0001H: Forward run
0002H: Reverse run
0003H: Forward Jog
0004H: Reverse Jog
0005H: Free stop (emergency stop)
0006H: Stop
0007H: Fault reset
2000H
0008H: Jog Stop
Inverter read status: (read-only)
Status word address
Status word function
0001H: Forward running
0002H: Reverse running
0003H: Inverter is in standby
3000H
0004H: Fault is happening
Parameter lock password verification: (If the return code is8888H, it indicates that
password verification is passed)
Password address
Enter password
1F00H *****
Parameter lock command: (write only)
Lock password
command address
Lock password command content
1F01H 55AAH
Inverter fault description:
Warranty
Card
- 109 -
Inverter fault address:
Fault code
Inverter fault information:
0000: No fault
E.oUt1
0001: Output phase loss
E.oUt2 0002:
Retain
E.oUt3
0003: Factory setting time
E.oC1
0004: Acceleration overcurrent
E.oC2
0005: Deceleration overcurrent
E.oC3
0006: Constant speed overcurrent
E.oU1
0007: Acceleration overvoltage
E.oU2
0008: Deceleration overvoltage
E.oU3
0009: Constant speed overvoltage
E.LU
000A: Bus undervoltage fault
E.oL1
000B: Motor Overload
E.oL2
000C: Inverter overload
E.oH2
0010: Inverter module overheating fault
E.SET
0011: External fault
E.CE
0012: Communication fault
E.oCC
0013: Current detection fault
E.TE
0014: Motor auto tunning fault
E.EEP
0015: EEPROM operation fault
8000H
E.PId
0016: PID disconnection fault
Data on communication failure information description (fault code) :
Communication fault message (fault code) : when the slave device responds,
function code field and fault address are used to indicate whether it is a normal response
(correct) or an error (called exception response) . If it is the normal response, the slave
device will respond corresponding function code and data address or sub-function code.
If it is the exception response, the slave device returns a code equivalent to the normal
code, but the first position is the logic 1.
For example: a message sent from one master device to one slave device is
required to read a set of inverter function code address data, it will produce the
following function code: 00000011 (hexadecimal 03H), for the normal response, the
slave device will respond the same function code. For the exception response, it
returns: 10000011 (hexadecimal 83H) . In addition to the modification to function code
for exception, the slave device will respond to a byte of exception code, which defines
the reason for exception occurrence.
When the application program of master device gets a exception response, the
typical handling process is to resend the message, or change corresponding fault
command.
MODBUS Exception Code Table
MODBUS exception code
Code
Name
Explanations
01H Password error
The password written into by the password authentication
Содержание CA-203A
Страница 1: ...Vector control inverter Operating manual CA Series www tpg tw com...
Страница 61: ...1 TPG Corp TPG Corp 1 1 1 1 1 1 1 1 1 2 1 2...
Страница 62: ...2 1 2 U V W EMC P RB R S T U V W 3 U V W AC36V 1 3 1 500V 5M 2 3 0Hz 400Hz 50Hz 4 5 PWM...
Страница 63: ...4 6 PWM 7 8 CA 9 CA 10 11 1000m 12 13 14 1 2 3 4 5 15 1 U V W 2 3 4 5 5 6 MOS IGBT 7 E 8 CE 1 4...
Страница 70: ...18 4 7 CA Series K1 K1 K1 R S T MC1 MC2 MC1 MC2 M 3 4 5 19 4 8 4 6 R S T...
Страница 101: ...80 7 1 3 7 3 81 8 1 6 LED OLED 2 1 R S T U V W IGBT 8 2...
Страница 109: ...MODBUS 05H 06H 07H 08H EPPROM...