Chapter 5 Function parameter
50
8: Free stop
9: Fault reset
10: External fault input
11: Frequency change
settings clear
12: Multi-speed terminal
1
13: Multi-speed terminal
2
14: Multi-speed terminal
3
15: Multi-speed terminal
4
16: Ac/deceleration time
selection
17: Control command
switch terminal
18: Ac/deceleration
prohibited
19: PID control pause
20: Wobbulate pause
(stops at the current
frequency)
21: Wobbulate reset
(returns to the center
frequency)
22: Torque control
prohibited
23: Frequency change
settings temporarily clear
24: Stop DC braking
25: Reserved
This parameter is used to set functions of digital multi-function input terminals.
0: No function
1: Forward run (FWD)
2: Reverse run (REV)
External terminals are used to control the FWD/REV run mode of inverter.
3: Three-wire operation control: this terminal is used to determine the three-wire
operation control mode of the inverter;For details, see the introduction of F1.06 three-
wire function code.
4: Forward Jog
5: Reverse Jog
For the specific Jog running frequency and Jog Ac/deceleration time, please see
the instructions of F7.00 to F7.02 function code.
6: Frequency setting increment (UP)
7: Frequency setting decrement (DOWN)
Modify frequency increment/decrement command when the frequency is
referenced by external terminal. Adjust up/down the set frequency when the digital
setting is selected as the frequency source.
Chapter 5 Function parameter
51
8: Free stop: once command is enabled, the inverter immediately blocks output but
can not control the process of motor stop, the mode is recommended for the application
of large inertia load and no requirement for stop time, the mode is same as the free stop
described in F3.05.
9: Fault reset: external fault reset function for remote fault reset, it has same
function as the STOP/RESET key on the keyboard.
10: External fault input: when this signal is active, the inverter will report external
faults (E.SET) and stop.
11: Clear frequency change setting: modify setting frequency by using external
terminals, UP as increment command, DOWN as decrement command, the function is
used to clear the frequency value set by UP/DOWN so that setting frequency gets back
to the frequency set by the frequency command channel.
12,13,14,15:the multi-speed terminal 1 to 4 can achieve a 16-speed setting through
this combination of four terminals. Note: multi-speed terminal 1 is low, multi-speed
terminal 4 is high. See E1 group.
Multi-speed 4
Multi-speed 3
Multi-speed 2
Multi-speed
1
BIT3
BIT2
BIT1
BIT0
16: Ac/deceleration time selection terminals: used to select acceleration and
deceleration time group:
Terminals
Ac/deceleration time selection
Parameters
OFF
Ac/deceleration time 1
F0.05
、
F0.06
ON
Ac/deceleration time 2
F7.03
、
F7.04
17: Control command switch terminal: when the command source is not from
keyboard control, the switching between command source and keyboard control can be
archived. For example, if the terminal control (F0.04 = 1) is active, this terminal can
switch between terminal control with keyboard control; if communication control
(F0.04 = 2) is active, this terminal can switch between communication control and
keyboard control.
18: Ac/deceleration prohibited: ensure the inverter is free from external signals
affect (except for shutdown command), maintain current output frequency.
19: PID control pause: PID temporary failure, the inverter maintains the current
frequency output.
20: Wobbulate pause: the inverter pauses the current output, when the function is
revoked, the inverter will continue wobbulate at the current frequency.
21: Wobbulate reset: the set frequency of inverter gets back to the center
frequency.
22: Torque control prohibited: the Inverter switches from torque control mode to
speed control mode.
23: Temporarily clear frequency change setting:the frequency value set by "UP"
and "DOWN" keyboard can be cleared when the terminal is connected so that for the
set frequency gets back to the frequency set by command channel, return the frequency
value set by frequency change setting again when the terminal is disconnected.
24: Stop DC braking: during the process of deceleration stop, when the terminal is
connected, the inverter will immediately perform DC braking, the braking state is
determined by F3.07 ~ F3.09.
Содержание CA-203A
Страница 1: ...Vector control inverter Operating manual CA Series www tpg tw com...
Страница 61: ...1 TPG Corp TPG Corp 1 1 1 1 1 1 1 1 1 2 1 2...
Страница 62: ...2 1 2 U V W EMC P RB R S T U V W 3 U V W AC36V 1 3 1 500V 5M 2 3 0Hz 400Hz 50Hz 4 5 PWM...
Страница 63: ...4 6 PWM 7 8 CA 9 CA 10 11 1000m 12 13 14 1 2 3 4 5 15 1 U V W 2 3 4 5 5 6 MOS IGBT 7 E 8 CE 1 4...
Страница 70: ...18 4 7 CA Series K1 K1 K1 R S T MC1 MC2 MC1 MC2 M 3 4 5 19 4 8 4 6 R S T...
Страница 101: ...80 7 1 3 7 3 81 8 1 6 LED OLED 2 1 R S T U V W IGBT 8 2...
Страница 109: ...MODBUS 05H 06H 07H 08H EPPROM...