21
(B) Up to 512 indoor units
Device
Touch Screen Controller
Intelligent Server
Intelligent Server Software
TCS-NET Relay Interface
Energy Monitoring Relay
Interface
Digital I/O Relay Interface
Ethernet wire
Switching HUB
PC
Power meter
Remarks
Same quantity as Intelligent Server
required
*
2
Up to 8 units per Intelligent Server
*
3
Up to 4 units per Intelligent Server
*
3
Up to 4 units per Intelligent Server
Category5 UTP straight cable
10 BASE-T compliant *
4
number of ports: As required
OS: Windows 2000 or later
Excel: Excel 2000 or later
Pulse output type
Pulse generator constants:
1kWh/pulse or 10kWh/pulse
Pulse duration: 50 - 1000 ms
Output terminal: ON/OFFcontactor
Model
BMS-TP5120PWE
BMS-LSV2E
BMS-STCC01E
BMS-IFLSV1E
BMS-IFWH3E
BMS-IFDD01E
Procured on site
Procured on site
Procured on site
Procured on site
Quantity
1
Max. 4
Max. 4
Max. 32*
2
Max. 16*
3
Max. 16*
3
*
1
1
1
*
5
*1 The number of ethernet wire and the number of switching HUB port vary with the number of Intelligent servers connected.
*4 100BASE-T compliant HUB is required in using 5 or more servers, or 2 or more controllers.
*5 The number of power meters vary with power meter specifications.
• Two or more refirgerant system can be connected to one power meter.
• For heat recovery VRF (SHRM) and “Super digital inverter”, “Digital inverter”, it is necessary to install the power meter
independently.
• All power meters connected same controller must be set same pulse generator constants.
Содержание BMS-TP0640ACE
Страница 1: ...FILE NO A04 016 TCS NET AIR CONDITIONING CONTROL SYSTEM TOUCHSCREENCONTROLLER TENTATIVE ...
Страница 16: ...16 ...
Страница 17: ...17 2 SYSTEM CONFIGURATION 2 1 Touch screen controller system configuration ...
Страница 22: ...22 ...
Страница 54: ...54 ...
Страница 96: ...96 ...
Страница 103: ...103 ...
Страница 104: ......