92
4-4-2 Setting for Intelligent server
Installing CF (Compact Flash) card
RS-485 operation mode setting
• Do not insert or remove the CF (Compact Flash) card during power on of the Intelligent Server.
Doing so may cause a failure.
• If the CF (Compact Flash) card is not inserted properly, the Intelligent Server will not work.
REQUIREMENT
Insert the attached CF (Compact Flash) card fully into the CF (Compact Flash) card slot on the side of
the Intelligent Server.
CF (Compact Flash) card
CF (Compact Flash) card slot
1
ON
2
3
4
1
2
3
4
OFF
ON
ON
OFF
1
2
3
4
RS-485 mode set
switch
AC inlet side
LED indicator side
The RS-485 mode set switch is provided on the bottom board of the Intelligent Server.
Set the switch as follows:
If the RS-485 mode set switch is set
incorrectly, the Intelligent Server will
not work.
NOTE
1
2
3
4
Not used
(Note 1) Transmit data sent from the Intelligent Server is not received by
the same server during transmission.
(Note 2) Transmit data sent from the Intelligent Server is also received
by the same server during transmission.
ON
OFF
ON
OFF
ON
OFF
A terminator resistor is connected between TX(+) and TX(-).
No terminator resistor is connected between TX(+) and TX(-).
A terminator resistor is connected between RX(+) and RX(-).
No terminator resistor is connected between RX(+) and RX(-).
Half-duplex mode (Note 1)
Full-duplex mode (Note 2)
Intelligent Server
Software
(BMS-STCC01E)
Intelligent Server
(BMS-LSV2E)
Содержание BMS-TP0640ACE
Страница 1: ...FILE NO A04 016 TCS NET AIR CONDITIONING CONTROL SYSTEM TOUCHSCREENCONTROLLER TENTATIVE ...
Страница 16: ...16 ...
Страница 17: ...17 2 SYSTEM CONFIGURATION 2 1 Touch screen controller system configuration ...
Страница 22: ...22 ...
Страница 54: ...54 ...
Страница 96: ...96 ...
Страница 103: ...103 ...
Страница 104: ......