POINT 3
When the central control is performed for indoor units of twin control in a group control, it may be required
to change the group address. (Adapter is attached to the header indoor unit.)
Reason
: The central control device communicates with individual indoor unit, header indoor unit of the
group control, and header indoor unit of twin control. However, as the address is automatically
set up, which unit will become the header unit is indefinite. Therefore if the unit attached with
adapter would not become the header indoor unit, a central control is unavailable.
How to check group address (Header/Follower indoor unit setup)
* Check the group address after confirming which unit is attached with the adapter.
<Procedure> Operation while air conditioner stops.
1
Push
SET
+
CL
+
buttons simultaneously for 4 seconds or more.
2
The indoor unit in which the fan is turned on is the header indoor unit.
Indoor unit in which the fan is turned on = Indoor unit with the adapter : To
Case 1
Indoor unit in which the fan is turned on = Indoor unit with the adapter : To
Case 2
*Adapter
Central
control
devices
Central control wiring
System A
System B
System C
Outdoor
*TCB-PCNT30TLE
Indoor
(Header)
Remote
controller
Outdoor
Indoor
(Follower)
*Adapter
Outdoor
Indoor
(Follower
Header)
Remote
controller
Outdoor
Indoor
(Follower)
Outdoor
Indoor
(Header
Follower)
*Adapter
Outdoor
Indoor
Remote
controller
Line address
Indoor unit address
Group address
1
1
1
2
1
2
3
1
2
4
1
2
1
2
5
1
1
6
1
0
Central control is possible.
Central control is possible.
Central control is impossible.
* A wired remote controller (RBC-AMT21E)
is required for address change.
Содержание BMS-TP0640ACE
Страница 1: ...FILE NO A04 016 TCS NET AIR CONDITIONING CONTROL SYSTEM TOUCHSCREENCONTROLLER TENTATIVE ...
Страница 16: ...16 ...
Страница 17: ...17 2 SYSTEM CONFIGURATION 2 1 Touch screen controller system configuration ...
Страница 22: ...22 ...
Страница 54: ...54 ...
Страница 96: ...96 ...
Страница 103: ...103 ...
Страница 104: ......