50
If an inductive load (relay coil) or a bulb is connected, a surge voltage or rush current will be
generated. Take adequate measures against surge voltage or rush current.
CAUTION
Wiring Connection
The following describes wiring connections of the Digital I/O Relay Interface when it is used in the air
conditioner control system.
• Terminator resistor setting
Set the RS-485 terminator resistor by the TCS-NET Relay Interface.
Do not set it by the Digital I/O Relay Interface.
• Shield earthing
The shield earth of the RS-485 signal wires should be single-point earth. Earth the wires on the
Intelligent Server.
Other shield lines should be closed, and the terminal end should be open and insulated.
• Connection of external digital inputs
Input circuit examples are shown below (electrically isolated using a photo-coupler).
(1) Example of contact input connection
(2) Example of current sink connection
12V
12V
Contact
Input terminal
DI-1 to DI-8
Current sink
Input terminal
DI-1 to DI-8
• Connection of external digital outputs
Output circuit examples are shown below (open collector output electrically isolated using a photo-
coupler).
(1) Example of load connection
(2) Example of load connection
12V
GND
12V
+12V
Output terminal
DO1 to DO4
Load
External
power
supply
Output terminal
DO1 to DO4
Содержание BMS-TP0640ACE
Страница 1: ...FILE NO A04 016 TCS NET AIR CONDITIONING CONTROL SYSTEM TOUCHSCREENCONTROLLER TENTATIVE ...
Страница 16: ...16 ...
Страница 17: ...17 2 SYSTEM CONFIGURATION 2 1 Touch screen controller system configuration ...
Страница 22: ...22 ...
Страница 54: ...54 ...
Страница 96: ...96 ...
Страница 103: ...103 ...
Страница 104: ......