66
4-3-1 (3) Line (System) address setting
CAUTION
Be sure to allocate different line address for each refrigerant system as much as possible even if
there are two or more TCS-NET relay interfaces.
SW11
1
ON
Header unit interface P.C. board
2 3 4
SW12
1
ON
2 3 4
SW06
1
ON
2 3 4
SW07
1
ON
ON
ON
ON
2 3 4
SW09
SW08
1
1
2 3 4
SW10
1 2 3 4
SW13
1
ON
2 3 4
SW14
1
ON
2 3 4
1. Using SW13 and 14 on the interface P.C.
board of the header unit in each system, set
up the system address for each system.
(At shipment from factory: Set to Address 1)
Note)
Be careful not to duplicate with other
refrigerant line.
System
address
1
2
3
4
5
6
7
8
9
10
11
12
13
14
SW13
SW14
1
2
3
4
1
2
3
4
×
×
×
×
×
×
{
×
×
×
×
×
{
×
×
×
{
{
×
×
×
×
×
{
×
×
{
×
{
×
×
×
{
{
×
×
{
{
{
×
×
×
×
×
{
×
{
×
×
{
×
×
{
×
{
×
{
{
×
{
×
×
×
{
{
×
{
×
{
{
System
address
15
16
17
18
19
20
21
22
23
24
25
26
27
28
SW13
SW14
1
2
3
4
1
2
3
4
×
×
{
{
{
×
{
{
{
{
{
×
×
×
×
{
{
×
×
×
{
×
{
×
×
{
{
{
×
×
{
×
×
{
×
{
{
×
{
×
{
×
{
{
×
{
{
{
{
×
{
×
×
×
{
{
{
×
×
{
{
×
{
×
{
{
{
{
×
{
2. Check that the relay connectors between [U1U2] and [U3U4] terminals are come out in all the header
units to which the central control is connected.
(At shipment from factory: No connection of connector)
System address switch on outdoor interface P.C. board
: Is not used for setup of system address. (Do not change setup.)
(
{
: Switch ON, × : Switch OFF)
4-3-1 (4) Power reset
• To activate line address on both outdoor and indoor unit side, power supply is temporarily reset.
• When power is supplied again, be sure to the power of indoor unit prior to the outdoor unit.
Содержание BMS-TP0640ACE
Страница 1: ...FILE NO A04 016 TCS NET AIR CONDITIONING CONTROL SYSTEM TOUCHSCREENCONTROLLER TENTATIVE ...
Страница 16: ...16 ...
Страница 17: ...17 2 SYSTEM CONFIGURATION 2 1 Touch screen controller system configuration ...
Страница 22: ...22 ...
Страница 54: ...54 ...
Страница 96: ...96 ...
Страница 103: ...103 ...
Страница 104: ......