69
TCS-NET
relay
i n t e r fa c e
Header
Header
Header
U3 U4
ON
1 2
OFF
SW30
U1 U2
U5 U6
ON
1 2
OFF
SW30
ON
1 2
OFF
SW30
ON
1 2
OFF
SW30
ON
1 2
OFF
SW30
U3 U4
U1 U2
U5 U6
U3 U4
U1 U2
U5 U6
U3 U4
U1 U2
U5 U6
U3 U4
U1 U2
U5 U6
Refrigerant system
1
Refrigerant system
2
Refrigerant
system
3
Check that relay connector are connected in all header
outdoor units to which TCS-NET relay interface is
connected.
TCS-NET
relay
i n t e r fa c e
Header
Header
Header
U3 U4
ON
1 2
OFF
SW30
U1 U2
U5 U6
ON
1 2
OFF
SW30
ON
1 2
OFF
SW30
ON
1 2
OFF
SW30
ON
1 2
OFF
SW30
U3 U4
U1 U2
U5 U6
U3 U4
U1 U2
U5 U6
U3 U4
U1 U2
U5 U6
U3 U4
U1 U2
U5 U6
SW30-2 should be OFF in all header outdoor units
except the header unit with the smallest line address.
Refrigerant system
1
Refrigerant system
2
Rrefrigerant
system
3