64
4-3-1 (2) Manual setting from wired remote controller
CAUTION
Be sure to allocate Line (system) /Group/Indoor address one by one to match the address setting
table and setup file that is prepared beforehand.
If wrong value is set, a problem such as error of communication with air conditioner will occur.
Indoor, group, line
address are set
manually for each
refrigerant system
one by one.
Line address
(At shipment:1)
Header
Outdoor unit
Indoor unit
Indoor address
1
2
3
4
0
0
1
2
Group address
1
1
1
1
Line address
Remote
controller
Follower
At shipment, all address are 0099 (Address unset status)
Dip Switch setting
on interface P.C.board
(Step 1)
Arrange one indoor unit and one remote controller (RBC-AMT21E) set to 1 by 1.
Note
:Don’t use simple remote controller or wireless remote controller.
(Address setting is not available.)
Connect wired remote
controller individually
when manual address
setting