System Configuration Table
Air conditioning monitoring/control
Energy monitoring and billing
Indoor units connected
Intelligent Server
Intelligent Server Software
TCS-NET Relay I/F
Energy Monitoring Relay I/F
Digital I/O Relay I/F
Touch Screen Controller
BMS-TP0640ACE BMS-TP0640PWE BMS-TP5120ACE BMS-TP5120PWE
×
–
×
Max. 64 units
1 unit
1 unit
Max. 8 units
–
Max. 4 units
Max. 4 units
Function
BMS-LSV2E
BMS-STCC01E
BMS-IFLSV1E
BMS-IFWH3E
BMS-IFDD01E
Component
×
–
×
Max. 512 units
Max. 4 units
1 unit per Intelligent Server
(max. 4 units in total)
Up to 8 units per Intelligent Server
(max. 32 units in total)
–
Max. 4 units
Max. 4 units
(× ... available – ... not available)
Switching HUB
Ethernet wire
PC
Power meter
Procured on site
Procured on site
Procured on site
Procured on site
*
1
*
3
Category 5 UTP straight wire
OS: Windows 2000 or later, Excel 2000 or later
Pulse output type
Pulse generator constants:
1 kWh/pulse or 10 kWh/pulse
Pulse duration: 50 - 1000 ms
Output terminal: ON/OFF contactor
Comply with 10BASE-T
*
2
Number of ports: As required
*
1:The number of ethernet wires and the number of switching HUB port vary with the number of Intelligent Server connected.
*
2:100 BASE-T compliant is required in using 5 or more server, or 2 or more controllers.
*
3:The number of power meters vary with power meter specifications.
• Two or more refirgerant system can be connected to one power meter.
• For heat recovery VRF (SHRM) and “Super digital inverter”, “Digital inverter”, it is necessary to install the power meter
independently.
• All power meters connected same controller must be set same pulse generator constants.
Содержание BMS-TP0640ACE
Страница 1: ...FILE NO A04 016 TCS NET AIR CONDITIONING CONTROL SYSTEM TOUCHSCREENCONTROLLER TENTATIVE ...
Страница 16: ...16 ...
Страница 17: ...17 2 SYSTEM CONFIGURATION 2 1 Touch screen controller system configuration ...
Страница 22: ...22 ...
Страница 54: ...54 ...
Страница 96: ...96 ...
Страница 103: ...103 ...
Страница 104: ......