68
4-3-1 (7) Setup of relay connector and terminator
• After trial operation for each refrigerant system, set the relay connector and terminator resistor for all
refrigerant system which are connected from one TCS-NET relay interface.
<Procedure>
1
How to set up terminator resistor (SW30)
When all the address setups have finished in the same
refrigerant system, put the terminator resistor (SW30) in the
same central control line into one.
• Remain only SW30-2 of the header outdoor unit with the
least line address number as it is ON.
(With terminal resistor)
• Set up SW30-2 of the other header outdoor units to OFF.
(Without terminal resistor)
2
Connect the relay connector between [U1U2] and
[U3U4] of the header outdoor unit for each refrigerant
system.
Header outdoor unit
interface P.C. board
SW11
1
ON
2 3 4
SW12
1
ON
2 3 4
SW06
1
ON
2 3 4
SW07
1
ON
ON
ON
ON
2 3 4
SW09
SW08
1
1
2 3 4
SW10
1 2 3 4
SW13
1
ON
2 3 4
SW14
1
ON
2 3 4
SW30
SW30
1
ON
2
1
2
U1 U2
For internal
wiring between
indoor and
outdoor
U3 U4
For wiring of
central control
system
U5 U6
For internal
wiring between
outdoor units
TCS-NET
Relay I/F
(BMS-IFLSV1E)
No.1
Main BUS
Main BUS
Ethernet
Touch Screen Controller
(BMS-TP0640/5120)
Switching HUB
PC for Energy
Monitoring
InteIligent Server
(BMS-LSV2E)
InteIligent Server
Software
(BMS-STCC01E)
RS-485
Line address
=1
Line address
=2
TCS-NET
Relay I/F
(BMS-IFLSV1E)
No.3
Main BUS
Main BUS
Line address
=4
Line address
=5
Main BUS
Line address
=6
TCS-NET
Relay I/F
(BMS-IFLSV1E)
No.2
Main BUS
Line address
=3
Compact
Flash
Range for each
setting procedure
<System diagram (example)>
Содержание BMS-TP0640ACE
Страница 1: ...FILE NO A04 016 TCS NET AIR CONDITIONING CONTROL SYSTEM TOUCHSCREENCONTROLLER TENTATIVE ...
Страница 16: ...16 ...
Страница 17: ...17 2 SYSTEM CONFIGURATION 2 1 Touch screen controller system configuration ...
Страница 22: ...22 ...
Страница 54: ...54 ...
Страница 96: ...96 ...
Страница 103: ...103 ...
Страница 104: ......