• To confirm all the unit numbers from an arbitrary wired remote controller;
<Procedure>
(Operation while the air conditioner stops)
The indoor unit No and position in the same refrigerant piping can be confirmed. An outdoor unit is selected, the
indoor unit numbers in the same refrigerant piping are successively displayed, and then its indoor unit fan is
turned on.
1
Push the timer time
+
buttons simultaneously for 4 seconds or more.
Firstly, the line 1,
item code
(Address Change) is displayed. (Select outdoor unit.)
3
Using the setup temp.
/
buttons,
set
to the item code.
4
Using the timer time
/
buttons, change
the displayed setup data to a data which you
want to change.
5
Push
SET
button.
6
Using the
UNIT
button, select the unit No. to
be changed at the next time. Repeat the proce-
dure
4
to
6
and change the indoor address so
that it is not duplicated.
7
After the above change, push
UNIT
button to
confirm the changed contents.
8
If it is acceptable, push
button to finish
confirmation.
2
Using
UNIT
+
buttons, select the line address.
3
Using
SET
button, determine the selected line address.
• The indoor unit address, which is connected to the refrig-
erant pipe of the selected outdoor unit is displayed and the
fan is turned on.
4
Every pushing
UNIT
button, the indoor unit numbers
in the identical pipe are successively displayed.
• Only fan of the selected indoor unit operates.
[To select another line address]
5
Push
CL
button to return to procedure
2
.
• The indoor address of another line can be successively
confirmed.
6
Push
button to finish the procedure.
4-3-1 (13) Address change from remote controller
Change of indoor address from wired remote controller
• To change the indoor address in individual operation (Wired remote controller : Indoor unit = 1 : 1) or
group control
(When the setup operation with automatic address has finished, this change is available.)
<Procedure>
(Operation while air conditioner stops)
1
Push simultaneously
SET
+
CL
+
buttons for 4 seconds or more.
(The firstly displayed unit No indicates the header unit in group control.)
2
In group control, select an indoor unit No to be changed by
UNIT
button.
(The fan of the selected indoor unit is turned on.)
Operation procedure
1
→
2
→
3
→
4
→
5
→
6
→
7
→
8
End
4
8
UNIT
SET
CL
UNIT No.
CODE No.
SET DATA
R.C. No.
1
5
2,
6,
7
3
Содержание BMS-TP0640ACE
Страница 1: ...FILE NO A04 016 TCS NET AIR CONDITIONING CONTROL SYSTEM TOUCHSCREENCONTROLLER TENTATIVE ...
Страница 16: ...16 ...
Страница 17: ...17 2 SYSTEM CONFIGURATION 2 1 Touch screen controller system configuration ...
Страница 22: ...22 ...
Страница 54: ...54 ...
Страница 96: ...96 ...
Страница 103: ...103 ...
Страница 104: ......