TMP High Performance Vector Control Inverter User Manual
67
Multi-frequency/speed is set in P2.09
~
P2.23, which can be used in multi-speed
running and programming state.
There are 15 multi-frequency operation modes, which can be selected through control
terminals.
Assumption:
“1 (ON)” means that control terminal is connected;
“0 (OFF)” means that control terminal is disconnected.
If control terminals of multi-frequency are not set, or all of them are in OFF position,
frequency setting is determined by function code P0.02;
If certain control terminal of multi-frequency is not in OFF position, frequency setting
is determined by function code P2.09~P2.23;
If multi-frequency operation is selected, Starting/stopping the drive is determined by
control mode selection P0.01.
Freque
ncy
Termin
al
1
X
2
X
3
X
4
X
5
X
6
X
7
X
8
X
9
X
10
X
11
X
12
X
13
X
14
X
15
X
Termin
al 1
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
Termin
al 2
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
Termin
al 3
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
Termin
al 4
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
P2.24 Jump frequency 1
Setting range: 0
~
400.0Hz
P2.25 Jump frequency 2
Setting range:0
~
400.0Hz
P2.26 Jump frequency 3
Setting range:0
~
400.0Hz
P2.27 Jump frequency range
Setting range:0
~
20.00Hz
Jump frequency is set to prevent the output frequency of inverter from meeting the
mechanical resonant point of load.
In Jump frequency parameters, set the system's mechanical resonant central frequency, at
most three frequency values can be setup, shown in Fig.6-8.