TMP High Performance Vector Control Inverter User Manual
106
not be saved.
1:
When undervoltage occurs during running, fault relay acts and fault code
will be saved. When undervoltage occurs during stop state, fault relay
does not act, and fault code will not be saved.
2:
When undervoltage occurs in running or stopping state, fault relay acts
and fault code will be saved.
Pd.14
Input phase loss function
Setting range
:
0
~
1
0
:
Disable
The
input phase loss function is disabled.
1
:
Enable
The
input phase loss function is enabled. ( only available on three phase input above 110kw
inverter)
Pd.15
Output phase loss function
Setting range
:
0
~
1
0: Disable
The
output phase loss function is disabled.
1
:
Enable
The
output phase loss function is enabled.
Pd.16
Under voltage point
Setting range
:
360
~
440
Default value is 400v (DC voltage). In some case when the input voltage is low or not stable,
the value can be adjusted to avoid under voltage fault.
PE Factory reserved
PE.00
~
PE.05
are reserved parameters for individual consumer.
PF Factory reserved
PF.00
~
PF.19
are reserved parameters for individual consumer.
PH Display function
PH.00
running
display
parameters
selection
Setting range
:
0
~
14
TMP drive has 15 state parameters in running state. User can scroll through
them by pressing ►► key during running process. Function code PH.00 defines
the default display parameter after starting, which includes:
0: Frequency setting