TMP High Performance Vector Control Inverter User Manual
6
1.3 Product Series
TMP
−
□□□
G-4 Three-phase 400V Constant torque/heavy-duty application
Power (kW)
0.75
1.5
2.2
4.0 5.5
7.5
11
15
18.5
22
30
37
45
55
75
Motor
power (kW)
0.75
1.5
2.2
4.0 5.5
7.5
11
15
18.5
22
30
37
45
55
75
Output
Voltage (V)
Three-phase 0 to rated input voltage
Rated current
(A)
2.5
3.8
5.5
9
13
17
24
30
39
45
60
75
91
112
15
0
Overload
capacity
1150% 1 minute, 180% 2 seconds, 200% 0.5 second, interval: 10 minutes (inverse time lag
feature)
Input
Rated
voltage/frequen
cy
Three-phase 380V/480V; 50Hz/60Hz
Allowable
voltage range
323V ~ 528V; Voltage unbalanceness
≤
3%; allowable frequency fluctuation: ±5%
Rated current
(A)
3.5
6.2
9.2 14.9 21.5 27.9
39
50.3
60
69.3
86
104 124 150
20
1
Braking unit
Built-in as standard
Built-in as option
Protection class
IP20
Cooling mode
Self-coolin
g
Forced air convection cooling
Power (kW)
90
110 132 160 185 200 220 250 280 315
355
400 450 500
Motor
power (kW)
90
110 132 160 185 200 220 250 280 315
355
400 450 500
Output
Voltage (V)
Three-phase 0 to rated input voltage
Rated current
(A)
176
210 253 304 350 380 426 470 520 600 650 690 775 860
Overload
capacity
150% 1 minute, 180% 10 seconds, 200% 0.5 second, interval: 10 minutes (inverse time lag
feature)
Input
Rated
voltage/frequen
cy
Three-phase 380V/480V; 50Hz/60Hz
Allowable
voltage range
323V ~ 528V; Voltage unbalancedness
≤
3%; allowable frequency fluctuation: ±5%
Rated current
(A)
160*
196
*
232
*
282
*
326
*
352
*
385
*
437
*
491
*
580
*
624
*
670
*
755
*
840
*
Braking unit
External braking unit needed
Protection class
IP20
Cooling mode
Forced air convection cooling
*TMP
−090G-4 and above products are equipped with external DC reactor as standard.