TMP High Performance Vector Control Inverter User Manual
53
pre-alarm detection
1: Detect all the time and alarm
Pd.05
Overload
detection
threshold
20.0~180.0%
150.0
225
+
Pd.06
Overload
pre-alarm
delay
0.0~60.0s
2.0
226
+
Pd.07
Auto current limiting
threshold
20.0~180.0%
150.0
227
+
Pd.08
Frequency
decrease
rate during current
limiting
0.00~99.99 Hz/s
0.00
228
+
Pd.09
Action mode of auto
current limiting
0: Disabled
1: Enabled during Acc/Dec, disabled at
constant speed
2: Enabled during Acc/Dec, enabled at constant
speed
1
229
+
Pd.10
Auto reset
0
:
Disabled
1~5
:
Times of fault reset
0
230
+
Pd.11
Auto reset interval
2.0~20.0s
2.0
231
+
Pd.12
Relay action in
Auto reset
0
:
No action
1
:
action
0
232
Pd.13
Act selection at under
voltage fault
0
:
No action
1
:
Act in running state
2
:
Act in running and stop state
1
233
+
Pd.14
Input phase loss
function
0
:
Disable
1
:
Enale
1
234
+
Pd.15
Output phase loss
function
0
:
Disable
1
:
Enale
1
235
+
Pd.16
Under Voltage Point
360-440
400
236
+
Pd.17
reserved
237
+
Pd.18
reserved
238
+
Pd.19
reserved
239
+