TMP High Performance Vector Control Inverter User Manual
8
1.4 Product Specifications
Item
Specifications
OUTPUT
Rated Output Voltage
Three phase 380V (Max output voltage is equal to input voltage)
Max continuous current
100% rated output current
Overload ability
150% rated current for 1minutes,
180% rated current for 2 seconds.
Output frequency
0Hz~400Hz
Input
Rated input voltage
Three phase: 380V±20%, 50~60Hz±5%
Control
performance
AVR Function,
When AVR function is enable
,
output voltage is stable under input voltage
fluctuation
Modulation modes
Optimized space voltage vector PWM modulation
Control mode
Sensorless Vector control; V/F control.
Running command input
modes
Panel control, external terminal control, control by serial port of host computer
Speed setting mode
Ten kinds of main frequencysetting modes, seven kinds of Auxiliary
frequencysetting modes. Several combination kinds of main frequencysetting
modes and Auxiliary frequencysetting modes.
Speed setup resolution
Digital setting: 0.01Hz.
Analog setting: highest frequency
×
0.1%
Voltage/Frequency
characteristic
Rated voltage: 50-100%,adjustable, Base frequency 50Hz, adjustable, five type
V/F curves
Speed control accuracy
Sensorless vector control:
±
0.05% rated speed(25
℃±
10
℃
)
Speed control range
vector control: 1:100
Starting torque
vector control: 150% rated torque at 0.5Hz.
Acc/dec characteristic
0.1seconde~3600 seconds
Braking torque
22 kW below: >20% rated torque,
30 kW above: >15% rated torque
Control I/O
Reference voltage output
1 channel, +10V, 50mA
Control voltage output
24V, 100mA