TMP High Performance Vector Control Inverter User Manual
65
2. In Acc/Dec Process, the parameters of S curve are set in symmetry.
P1.12 Restart after power failure
Setting range: 0, 1
0: Disabled;
1: Enabled; Function of restarting after power failure is enabled when the power supply
recovers.
P1.13 Delay time for restarting after power failure
Setting range: 0.0~20.0s
When the power recovers from failures, the time before the inverter restarts is the delay time.
This time is set according to the time needed by other equipment to recover when the power
supply recovers.
P1.14 dynamic braking start voltage
Setting range
:
630
~
710V
Setting the start voltage of dynamic braking.
P1.15 Rate of dynamic braking
Setting range: 0.0 ~100.0%
Define duty cycle of dynamic braking.
0: No dynamic braking
1%~100%: In process of dynamic braking, percentage of valid braking time to carrier cycle,
user can modify this value if necessary.
P1.16 Start frequency lower than frequency limit
Setting range:0, 1,2
0:when preset frequency is lower than low frequency limit, the inverter will not start;
1:when preset frequency is lower than low frequency limit, the inverter will start at low
frequency limit;
2:When preset frequency is lower than frequency limit, the inverter stop.
P1.17
MF key function
0
:
No operation
;
1
:
reverse rotation
P1.18
Stop/reset Key function
Setting range
:
0
、
1
、
2
This parameter decides the
“
stop
”
function of STOP/RESET key of the keypad
in different command source.The
”
Reset
”
function is usable in all command source.
0
:
action on keypad control mode
1
:
action on both keypad and
External terminal
2
:
action on both keypad and
communication
P1.19
Fan control function
Setting arrange
:
0
、
1
0
:
Cooling fan
always runs after power on
1
:
Cooling fan stops fan after inverter stop running
P2 Auxiliary function parameters 2
P2.00 ACC time2
Setting arrange
:
0.1
~
3600s
P2.01 ACC time2
Setting arrange
:
0.1
~
3600s
P2.02 ACC time3
Setting arrange
:
0.1
~
3600s
P2.03 ACC time3
Setting arrange
:
0.1
~
3600s