INSTALLATION
MOUNTING INSTRUCTIONS
Open the latch and lift the cover. Remove the black caps located on
each of the four mounting holes. Mount the enclosure on the wall
using four screws. Be sure the electrical knockouts are at the bottom
of the enclosure in order to prevent water from entering the control-
ler. Insert the screws in the mounting holes and tighten. Fasten the
four black caps provided with the controller onto the four mounting
holes. The enclosure must be mounted in a location that will allow the
cover to be completely opened right up against the wall.
CONNECTIONS
To connect the controller, refer to the wiring diagram enclosed with
this user's manual.
Set the voltage switch to the appropriate voltage.
Use the electrical knockouts provided at the bottom of the
enclosure. Do not make additional holes in the enclosure,
particularly on the side of the enclosure when using a computer
communications module.
It may be necessary to install a transformer in order to supply
the appropriate voltage to the heating unit.
ALARM CONNECTION:
There are two types of alarms on the mar-
ket. One type activates when current is cut off at its input, whereas
the other activates when current is supplied at its input. For an alarm
of the first type, use the NO terminal as shown on the wiring diagram.
For an alarm of the second type, use the NC terminal.
ALL WIRING MUST BE DONE BY AN AUTHORIZED
ELECTRICIAN AND MUST COMPLY WITH APPLICABLE
CODES, LAWS AND REGULATIONS. BE SURE POWER IS
OFF BEFORE DOING ANY WIRING TO AVOID ELECTRI-
CAL SHOCKS AND EQUIPMENT DAMAGE.
!
WARNING