29
TC5-8SDA rev.03
TC5-8SDA
Press the push-button. The current time off for Stage 1 flashes
on the display, alternating with the letters "
OFF
". If the ramping
option has been enabled, the actual time off value may differ
from the user-defined time off. When this is the case, the actual
time off value is displayed, alternating with the letters "
OFF
" and
"
co
".
3
Activating / Deactivating Ramping Option
Set the selection knob to
STAGE 1 — DIFFERENTIAL/RAMP-
ING
. The current Stage 1 differential flashes on the display.
Press the push-button. The on/off state of the ramping feature is
displayed, i.e. ON / OFF. Use the adjustment knob to set the
state to the desired value.
4
Activating / Deactivating Outside T° Compensation
Set the selection knob to
OUTSIDE T
o
— SETTINGS
. The
current outside temperature is displayed. If "
– – –
" is dis-
played, internal switch # 6 (outside temperature probe) is set to
off.
Press the push-button. The status of the compensation factor is
displayed, i.e. ON / OFF. Use the adjustment knob to set the
status to the desired value. After ten seconds, the display
returns to the outside temperature value.