Adjusting Max. Temperature Difference Between
Zones
When using zoned heating, a built-in protection will operate the fans
according to the probes of the zone with the highest temperature
whenever the temperature difference between zones is greater than
this parameter. The default value is 7.5°F (4.2°C) and values range
from 5°F to 40.0°F (2.8°C to 22.2°C).
Set the selection knob to
HEATER 2 — OFFSET/DIFF.
The
current heater offset is displayed, alternating with the letters
"
OFT
".
Press the push-button twice. The maximum temperature
difference between zones is displayed, alternating with the
letters "
dif Zon
".
Use the adjustment knob to adjust the temperature difference to
the desired value.