The last ventilation stage can be configured as a mist cooling stage.
The number of heating stages determines which stage this is.
ON
OFF
TIME ON
TIME OFF
The mist units operate according to a timer cycle. Time on is the
running time of the mist units and time off is the off time of the mist
units.
The other ventilation stages operate as explained above. To configure
the controller to operate a mist stage, set internal switch # 11 to ON.
The following diagram sums up the operation of the mist units.
NUMBER OF HEATING STAGES
MIST STAGE
0
8
1
7
2
6
MIST COOLING
Mist units turn off
Room
Temperature
Set Point
Mist
Mist Offset
OFF
Mist units turn on
in timer mode
Diff.