41
TC5-8SDA rev.03
HEATER SETTINGS
CASCADING HEATERS
When cascading heating is used, the temperature used is the average
room temperature (internal switch 9 is turned OFF). To use stages 7
and 8 for heating, set internal switches # 7 and 8 to ON. To use only
stage 8 for heating, set internal switch # 7 to ON and # 8 to OFF.
If the room temperature rises:
- at Set Point - Heater 1 Offset - Heater 1 Diff.: Heater 2 turns off.
- at Set Point - Heater 1 Offset: Heater 1 turns off.
If the room temperature falls:
- at Set Point - Heater 1 Offset - Heater 1 Diff.: Heater 1 turns on.
- at Set Point - Heater 1 Offset - Heater 1 Diff. - Heater 2 Diff.: Heater
2 turns on.
Room
Temperature
Heating
Set Point
Heater 1
HEATER 1
DIFFERENTIAL
Heater 2 OFF
Heater 2
Heater 2 ON
Heater 1 ON
Heater 1 OFF
HEATER 1
OFFSET
HEATER 2
DIFFERENTIAL