12
TC5-8SDA rev.03
TC5-8SDA
For each additional probe connected to the controller:
Press the push-button once again. If the probe is not defective, the
letters "
PR#
" (where # is the number of the input to which the
probe is connected) are displayed, alternating with the on/off state
of the probe and the temperature measured by the probe. If the
probe is defective, the letters "
PR#
" are displayed, alternating with
the on/off state of the probe and the letter "
P
".
Outside Probe:
If the outside probe
is defective, the display shows the
letter "
P
" when the parameter selec-
tion knob is set to
OUTSIDE T
o
.
HEATING / COOLING OPTIONS
Stages 7 and 8 can operate as heating or cooling stages.
•
Set switches # 7 and # 8 to
OFF
to use
both stages for cooling.
•
Set switch # 7 to
ON
and switch # 8 to
OFF
to use Stage 8 for heating and Stage 7 for
cooling.
•
Set switches # 7 and # 8 to
ON
to use both
stages for heating.
Note that if only one stage is used for heating, it must be Stage 8.
7
8
ON