53
ENGLISH
- Remove the burner;
- Remove the top panel (3);
- remove the insulating cover (4);
- remove the screws (5) and slide the flue gas chamber
out (6);
3
6
4
5
- remove the turbulators (7) and check them for wear and
fin angle (replace as necessary);
- use a flue brush (8) or other suitable tool;
8
7
- remove any displaced soot through the combustion
chamber hole.
Proceed as follows on completion of cleaning:
- refit the turbulators in the flue gas pipes, making sure
that they are correctly seated;
- replace all removed components in the opposite order.
b
Before repositioning the flue gas chamber closure, re-
place the expanded silicone seal.
External cleaning
Clean the boiler’s casing panels and control panel with a soft
cloth damped in soapy water.
To remove marks from the boiler casing, use a cloth damped in
a 50% mix of water and denatured alcohol or a suitable clean-
ing product.
Wipe the boiler dry after cleaning it.
a
Do not use abrasive products, petrol or triethylene.