31
ENGLISH
Menu
Par.
No.
Description
Range
Default
setting
ACQUA-
HOME 25
R BLU
Default
setting
ACQUA-
HOME 32
R BLU
UM
Access
2000
2203
Zone 2 heating setpoint in 0 and 3 heating modes
The thermal unit adjustment determines the boiler set-
point in heating mode, using the highest value among
the requests of all the active zones (Par. 1101, 1201,
1301)
If Zone 2 is configured as mixed, the value set in param-
eter 1113 will be used as setpoint.
BT: (Par.
2221, 45)
AT: (Par.
2221,Par.
2024)
70 (AT)
45 (BT)
70 (AT)
45 (BT)
°C
U
2000
2219
Zone 2 maximum heating setpoint at the minimum ex-
ternal temperature
The range of this parameter is limited by the values of
the Minimum (Par. 2023) and Maximum (Par. 2024) set-
points.
BT: (Par.
2221, 45)
AT: (Par.
2221,Par.
2024)
82 (AT)
45 (BT)
82 (AT)
45 (BT)
°C
I
2000
2221
Zone 2 minimum heating setpoint at basic external tem-
perature (Par. 2222)
It sets the minimum heating setpoint when the external
temperature is equal to the value set in parameter 2222
(basic external temperature).
BT: (20, Par.
2219)
AT: (Par.
2023,Par.
2219)
30 (AT)
20 (BT)
30 (AT)
20 (BT)
°C
I
2000
2220
Zone 2 minimum external temperature
It defines the minimum external temperature to which
the maximum heating setpoint Par. 2219 must be as-
sociated.
-20…5
-20
-20
°C
I
2000
2222
Zone 2 basic external temperature
It sets the external temperature at which the boiler set-
point must be reduced, according to the value defined
in parameter 2221.
5...30
20
20
°C
I
2000
2225
Zone 2 summer/winter switching
It blocks the heating request when the external temper-
ature is greater than this setpoint.
0...35
20
20
°C
I
2000
2230 Parallel shift of direct Zone/Zone 1 climatic curve
-10…10
0
0
°C
U
2000
2231 Zone 2 mild climate temperature compensation
0...20
0
0
°C
I
2000
2232
Zone 2 ambient temperature nominal value
When an OpenTherm (OT) ambient thermostat is con-
nected to the zone control accessory, this parameter is
not used.
5...35
20
20
°C
I
2000
2234 Compensation factor of Zone 2 external temperature
0...100
50
50
%
I
2000
2235 Zone 2 mixing valve closing time
0...240
140
140
sec
I
2000
2236 Zone 2 mixing valve PID P
0...99
5
5
I
2000
2237 Zone 2 mixing valve PID I
0...99
10
10
I
2000
2238 Zone 2 valve operating time
0...255
2
2
I
2000
2239 Supply Extra
Only for MIX Zone
0...20
5
5
°C
I
2000
2240 Zone 2 circulator post-circulating time
0...60
30
30
sec
I
2000
2241 Zone 2 delivery overtemperature protection
0...100
55
55
°C
I
2000
2242 Zone 2 overtemperature control time
0…240
0
0
min
I
2000
2243 Zone 2 overtemperature stand-by time
0…240
2
2
min
I
2000
2244 Zone 2 system reset time
0…240
2
2
min
I
Zone 3 Heating Settings
3000
3300
Use of Zone 3 control accessory
0 = NO
1 = Yes
If Zone 3 control accessory is used, AT and OT inputs
are not enabled. AT input is used only to enable the
night reduction on all the active zones (Par. 2001 = 2
and 3).
0…1
0
0
I
3000
3301
Zone 3 mode
0 = direct
1 = mixed
0…1
1
1
I
2000
2303
Zone 3 heating setpoint in 0 and 3 heating modes
The thermal unit adjustment determines the boiler set-
point in heating mode, using the highest value among
the requests of all the active zones (Par. 1101, 1201,
1301)
If Zone 3 is configured as mixed, the value set in param-
eter 1114 will be used as setpoint.
BT: (Par.
2321, 45)
AT: (Par.
2321,Par.
2024)
70 (AT)
45 (BT)
70 (AT)
45 (BT)
°C
U