33
ENGLISH
Menu
Par.
No.
Description
Range
Default
setting
ACQUA-
HOME 25
R BLU
Default
setting
ACQUA-
HOME 32
R BLU
UM
Access
2000
2048 DHW setpoint with instant production
40…70
45
45
°C
U
2000
2049
Circulator modulation in DHW mode
The circulator modulation can vary between 50% = 5
and 100% = 10
5...10
9
9
10*%
I
2000
2052
DCW minimum temperature setpoint of DHW exchang-
er (it activates pump and diverting valve on domestic
circuit)
10...35
25
25
°C
I
2000
2053
DCW maximum temperature setpoint of DHW exchang-
er (it deactivates pump and diverting valve on domestic
circuit)
10...35
25
25
°C
I
2000
2056 Boiler minimum holding temperature for DHW instant
production
20...82
60
60
°C
I
2000
2061 Boiler setpoint for DHW instant production
40...82
80
80
°C
I
2000
2062
∆T boiler switch-off setpoint for DHW production
0...3
1
1
°C
I
2000
2063
∆T boiler delivery / boiler return
5...40
15
15
°C
I
2000
2074
Burner anti-freeze protection
0 = NO
1 = Yes
0…1
1
1
I
2000
2075
Heating circuit anti-freeze protection
0 = NO
1 = Yes
0…1
1
1
I
2000
2076
DHW anti-freeze protection
0 = NO
1 = YES
0…1
1
1
I
2000
2077 DHW anti-freeze protection time
0...24
12
12
hours
I
2000
2099
Burner ignition stand-by time
It delays the burner ignition after the opening of the so-
lenoid valve on the fuel supply pipeline
0…60
0
0
sec
I
Error log
2000
9001 Last error logged
I
2000
9002 Second last error logged
I
2000
9003 Third last error logged
I
2000
9004 Fourth last error logged
I
2000
9005 Fifth last error logged
I
2000
9006 Sixth last error logged
I
2000
9007 Seventh last error logged
I
2000
9008 Eighth last error logged
I
2000
9009 Ninth last error logged
I
2000
9010 Tenth last error logged
I