39
ENGLISH
Mode 3
: continuous operation with fixed setpoint and night re-
duction with ambient thermostat (AT)
In this mode:
- External probe is not required.
- The OpenTherm (OT) communication is not enabled
and any OT thermostat connected is supplied but sig-
nals a “communication error”.
- Input 0-10V is not used.
- The Modbus communication is not enabled.
The fixed setpoint adjustment procedure is the same of mode
0. The only difference is that the request is always active and
the setpoint is decreased (night reduction) by the value de-
fined by the parameter 2133 upon the opening of the ambient
thermostat/heat request contact.
Par. No. Description
2103
Main Zone/Zone 1 setpoint in heating mode Par.
2001= 0 and 3.
The thermal unit adjustment determines the boiler
setpoint in heating mode, using the highest value
among the requests of all the active zones (Par.
1101, 1201, 1301).If Zone 1 is set as mixed, the
value set in parameter 1112 will be used as set-
point.
2023
Minimum heating setpoint.
2024
Maximum heating setpoint.
2133
Main Zone/Zone 1 setpoint night reduction in heat-
ing mode Par. 2001=2 or 3.
It defines by how many degrees the heating set-
point will be reduced at the opening of the ambient
thermostat (AT) contact.
The reduction of the delivery temperature affects
all the active heating zones and it can be used
when the AT terminal of every zone regulator is
jumpered.
T delivery
(°C)
T outside (°C)
Tset min (°C)
Tset max (°C)
Setpoint @TA=ON
Par. 2024
Par. 2023
Par. 2133
Par. 2103
Setpoint @TA=OFF
Mode 4
: operation with variable setpoint according to the value
of the input signal 0-10V
In this mode:
- External probe is not required.
- The OpenTherm (OT) communication is not enabled
and any OT thermostat connected is supplied but sig-
nals a “communication error”.
- The Modbus communication is not enabled. If a device
is connected to the Modbus, the values on the remote
device are not updated.
The parameters regulating such temperature are:
Par.
No.
Description
2023
It limits the minimum value that can be assigned to
the setpoint in heating mode.
2024
It limits the maximum value that can be assigned to
the setpoint in heating mode.
2025
It defines the delivery temperature minimum value in
heating mode (Par. 2001 = 4).
2026
It defines the delivery temperature maximum value
in heating mode (Par. 2001 = 4).
The operation set-point is adjusted on the basis of the following
curve:
T delivery
(°C)
Voltage (V)
Par. 2024
Par. 2025
Par. 2026
Par. 2023
Special functions
When a special function is active, a specific message is shown
on the display of the device control interface.
Frost protection
The anti-freeze protection function protects the system against
freezing.
When the anti-freeze function is active, the message “AFro” is
displayed.
The intervention modes are the following:
-
Boiler anti-freeze protection (Par. 2074):
If the tempera-
ture of the delivery probe of the device drops below
5°C the burner turns on and stays on until the deliv-
ery temperature exceeds 10°C (with the external probe
connected the protection activates only with external
temperature values < 10°C).
-
Heating circuit anti-freeze protection (Par. 2075):
If the
burner stays off for 6 consecutive hours the circulator of
the device will activate for 5 minutes. If the temperature
of the delivery probe of the device drops below 5°C the
burner turns on and stays on until the delivery temper-
ature exceeds 10°C (with the external probe connected
the protection activates only with external temperature
values < 10°C).