29
ENGLISH
Menu
Par.
No.
Description
Range
Default
setting
ACQUA-
HOME 25
R BLU
Default
setting
ACQUA-
HOME 32
R BLU
UM
Access
1000
1056 Total hours of operation in heating mode
h x 10
U
1000
1057 Total hours of operation in domestic mode
h x 10
U
1000
1058 Total hours of operation
h x 10
U
1000
1063 Input signal 0-10V
V
U
Heating general settings
2000
2001
Heating operating mode
0 = Operation with fixed setpoint and ambient thermo-
stat
1 = Operation with climatic curve and ambient thermo-
stat
2 = Continuous operation with climatic curve and night
reduction with ambient thermostat
3 = Continuous operation with fixed setpoint and night
reduction with ambient thermostat
4 = Operation with variable setpoint with input signal
0-10V
0…4
0
0
I
2000
2007 Switch-off hysteresis in heating mode
0…20
3
3
°C
I
2000
2008 Ignition hysteresis in heating mode
0…20
3
3
°C
I
2000
2005 Circulator post-circulating time in heating mode
10…900
120
120
sec
I
2000
2009
Burner restart time
It defines the stand-by time for a subsequent restart af-
ter a switch-off, regardless of the delivery temperature
decrease. If it goes below the value set in Par. 2010 the
thermal unit remains on.
10...900
180
180
sec
I
2000
2010
Temperature differential for burner restart
It defines the temperature difference below which the
burner restarts regardless of the elapsed time indicated
in Par. 2009.
0...20
16
16
°C
I
2000
2025 Minimum 0-10V input voltage in heating mode Par.
2001= 4
0...10
1
1
V
I
2000
2026 Maximum 0-10V input voltage in heating mode Par.
2001= 4
0...10
9
9
V
I
2000
2080
Anti-legionella function (it starts without RTCC)
0 = deactivated
1 = daily
2 = weekly
0...2
1
1
I
2000
2090
Venting function
0 = deactivated
1 = activated
0...1
1
1
I
2000
2096
Overtemperature protection
If the boiler temperature exceeds this value, the burn-
er turns off and the circulator continues its operation to
discharge the excessive heat.
85...95
85
85
°C
I
Direct Zone / Zone 1 Heating Settings
3000
3100
Use of Zone 1 control accessory
0 = NO
1 = Yes
If Zone 1 control accessory is used, AT and AP inputs
are not enabled. AT input is used only to enable the
night reduction on all the active zones (Par. 2001 = 2
and 3)
0…1
0
0
I
3000
3101
Zone 1 mode
0 = direct
1 = mixed
0…1
1
1
I
2000
2103
Direct Zone/Zone 1 setpoint in heating mode Par. 2001=
0 and 3
The thermal unit adjustment determines the boiler set-
point in heating mode, using the highest value among
the requests of all the active zones (Par. 1101, 1201,
1301)
If Zone 1 is configured as mixed, the value set in param-
eter 1112 will be used as setpoint
If Zone 1
is not ena-
bled:
(Par. 2121,
Par. 2024)
If Zone 1 is
enabled:
BT: (Par.
2121, 45)
AT: (Par.
2121,Par.
2024)
70 (AT)
45 (BT)
70 (AT)
45 (BT)
°C
U