- Check that the thermal unit has come to a complete
stop by setting the main switch of the equipment and
the main switch of the system to “off”.
If all the requirements are fulfilled, restart the thermal unit and
carry out the analysis of the combustion products by enabling
the test mode (Par. 200 = 1).
During the test mode (chimney sweeper), the equipment works
at the maximum power for a time period of 15 minutes, then it
is automatically disabled.
Once the analysis of the combustion products is complete,
disable the function (Par. 200 = 0).
L
≥
5°
(*)
(*) The sampling hole for flue gas analysis must be made
on the straight section of the discharge duct, sufficiently far
from curves and elbows. For the hole size and its correct
positioning on the discharge duct (minimum or maximum
distance from the equipment outlet to be observed), refer to
the regulations in force.
b
Always plug the sampling hole after analysing the flue
gases.
Burner control and adjustment
ADJUSTING PUMP PRESSURE
Turn the adjuster screw (1) to achieve the pressure setting
specified in the table.
1
2
3
4
5
0
6
1
ACQUAHOME
25 R BLU
(*)
ACQUAHOME
32 R BLU
(*)
Adjusting pump pressure
11,5 bar
14,5 bar
(*)
Burner with oil heater
ADJUSTING THE AIR DAMPER
The air damper can be adjusted without removing the burner
cover.
- Use an Allen key to turn the adjuster screw (1) to
achieve the required setting on the graduated scale (2)
2
1
ACQUAHOME
25 R BLU
(*)
ACQUAHOME
32 R BLU
(*)
Adjusting the air damper
3,6
1,8
(*)
Burner with oil heater