43
Z1 AUX
ADDRESS
2017
OPERATION
217 + 01
TEXT MENU
4. INPUTS – 5. ZONES – 01. ZONE – 7. AUXILIARY
Setting of Auxiliary Attributes for Zone 01
At this address are assigned
only attributes for Auxiliary type zone
.
Only one attribute AUX can be assigned at this address - a number from 0 to 9. To assign an AUX
attribute press the respective digital number. The entered attribute is confirmed with ENTER.
The following Attributes are available for setting at this address:
No
Attribute
Description
0
24h Burglary alarm
zone
With this attribute assigned, the zone will be active irrespective
of the arming type. The zone will operate as SLEEP type and
the programmable ALARM and SIREN outputs, and the system
communicator will be activated.
1
AC loss
Main power supply lost.
2
Battery low
Low battery charging level.
3
Water leakage
Activated flood detector.
4
Gas detector
Activated gas detector.
5
GSM link trouble
GSM communication failure.
6
Low Bottled Gas Level
Activated low bottled gas detector.
7
High Temperature
High temperature in the premises.
8
Low Temperature
Low temperature in the premises.
9
Loss of Heat
Loss of heat in the premises.
Default setting: 0. 24h Burglary
Z1 NAME
ADDRESS
2018
OPERATION
218 + 01
TEXT MENU
4. INPUTS – 5. ZONES – 01. ZONE – 8. NAME
Programming of the Zone 01 Name
The engineer can enter a new name for Zone 01 at this address. The name has to be up 16
symbols
– letters (small and capital), digits and special symbols, including spaces.
The letters can be entered directly by the digit buttons. The cursor moves automatically to the right
after choosing of letter or digit, or may be moved manually by the arrows. To enter a digit, press the
respective button and hold it for 2-3 seconds. See also item 2.8. Entering text for LCD Keyboard.
Confirm the new zone name with ENTER button.
Default name: Zone 01