Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
22
CHIME
ADDRESS
0012
OPERATION
012
TEXT MENU
2. SETTINGS – 02. CHIME
Chime Sound Signalization
At this address, you set the parameter as:
DISABLE
The “Chime” sound signalization is deactivated.
ENABLE
The “Chime” sound signalization is activated.
At this address, the engineer can enable or disable the “Chime” sound signalization activated for
opening of entry-exit type zones.
The parameter status can be changed with pressing of random button of the keyboard. The change
is confirmed with ENTER button.
Parameter by default: ENABLED
TRBL
SOUNDS
ADDRESS
0013
OPERATION
013
TEXT MENU
2. SETTINGS – 03. TRBL SOUNDS
The trouble sound indication (two short beeps in every 20 seconds) from the keyboard in Technical
Trouble mode is assigned at this address.
The sound signalization is available for the following troubles:
1. AC Loss
Main power supply loss.
2. Battery Trouble
Battery low charge or missing.
3. Blown fuse
Fuse burnt out.
4. Tel. line TRBL/
Comm. Fail
Telephone line trouble & no communication with central
monitoring station.
5. Tamper
Open tamper in the system.
6. Sysbus error
Error on the system bus, i.e. possible short circuit or lost device.
7. Fire line error
Fire Detector Loss; Broken fire line.
8. Sounder fault
Possible problem or siren missing.
It is possible after the initial startup of the system a trouble message for 8. SOUNDER FAULT to be
displayed on the screen of LCD keyboards (8 zone number lights on the LED display). That
indicates some problems with sounder connected to PGM5. If case the PGM5 is used as a standard
output, you have to terminate it with 1kOm resistor, or to program it as regular output
– disable
option 1 at ADDRESS 3051.
The trouble sound signalization is enabling with pressing a button with the respective number from 1
to 8.
Pressing the button with the same number again will disable the trouble indication for the
respective technical problem.
To disable/ enable all trouble sounds
press button “0” – the button alternatively switches over all
enabled / all disabled state.
The set parameters are confirmed with pressing the ENTER button.
Parameter by default: All ENABLED