Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
41
2
Fire
Delay
The siren and outputs siren type will be activated but the communicator starts
waiting for 30 up to 90 seconds according the fire delay operation algorithm
– refer
to the algorithm diagram in APPENDIX 3.
3
Report
Only
Silent alarm.
Only the programmable outputs PANIC type and the communicator are activated.
There is no memory indication on the keyboards. After entering of valid user code
the MEMORY button (LED) lights on together with the number of the activated
zone.
4
Video on
ARMED
Video recording of alarm events
In case of alarm event the VIDEO ON ARMED outputs will be activated for 1
minute.
5
Write to
LOG
Write to LOG file
Every zone activation and restoring, irrespective of the system arming status, will
be recorded in the system LOG file.
The attribute “Write to log” concerns the events OPEN (zone activation) and
CLOSE (zone restoring). This attribute is valid for all type of zones except the
zones TAMPER type. If the zone is set w
ith TAMPER type (at ADDRESS 2хх1 is
set type 6) the programming of this attribute has no matter.
6
Chime
“Chime” mode.
This parameter enables the sound signalization (Chime) for opening of an entry-
exit type zone when the system is disarmed.
7
Pulse
Count
Pulse count mode
.
This setting provides counting of short impulses 2- 4ms for the programmed time
at ADDRESS 2004 (OPERATION 204). The number of impulses is set at
ADDRESS 2003 (OPERATION 203) as value in range 1 to 9. The 0 value blocks
the Pulse Count mode and the zone can then function with the regular time for
detecting activation.
When the counter reaches the set number of impulses in the programmed period,
an alarm is triggered off. If the number of pulses is not reached in the programmed
period, the counter is restored.
This operation mode is applicable for connecting of rolling shutters detector to the
zone.
The wiring diagram for connecting of rolling shutters detector is:
8
Power up
Delay
The zone will be bypassed for a 120 second period after power-up of the system
(that eliminated the false alarms in the initial power-up of the control panel).
Default setting: 8. POWER UP DELAY
Table for Availability of Attributes according the zone type:
Attribute
Zone Type
Entry/ Exit
Follow
Instant
Fire
Panic
Tamper
Medical
Key-Switch
AUX
Mai
n
1. AutoBypass
2. Bypass
3. Stay ARM
4. SLEEP ARM
5. Force ARM
6. DOUBLE
7. E/E Final
8. Fast/ Regular
A
dd
3. Report only