70 Chapter 7 - Parameters Description
User Manual
36
freq<thr2
Output frequency < than
P.442
&
P.443
values
37
HS temp=thr
Heatsink temp = to
P.480
&
P.481
values
38
HS temp!=thr
Heatsink temp
≠≠≠≠≠
of
P.480
&
P.481
values
39
HS temp>thr
Heatsink temp > than
P.480
&
P.481
values
40
HS temp<thr
Heatsink temp < than
P.480
&
P.481
values
41
Output freq
Frequency in synchronism with output frequency
42
Out freq x 2
Frequency value x 2 in synchronism with output frequency
43
OutCoastThru
Coast Through stopping
44
OutEmgStop
Emergency stop
(*) see chapter 7.7, section PID Limit.
Code
Name
[Code] & Function.
Default
MIN
MAX
Unit
Variation
IP
I.100
Dig output 1 cfg
See Digital Outputs selection list
0
0
44
112
The digital outputs are FACTORY set as follow:
Dig output 1 cfg
- relay type (Terminal 1 - 2 - 3) =
0 Drive Ready
Analog Inputs Regulation Board
The drawing below, describes the block diagram of the standard "Analog Inputs" of the drive.
Terminal
10 bits+sign
converer
Filtro
T Delay
AN-INPUT
I 204
Offset
I 201
Monitor
d 202
Selection
Ref. Type
I 200
Gain
I 202
+
+
X
min
I 203
Clipping
I 205
I 203
I 205
OUT
IN
To Drive
Monitor
d 201
Figure 7.4.1: Analog Inputs
The regulation board provides as standard analog inputs.
Analog inputs resolution:
voltage input setting:
11 bits (10 bits + sign)
current input setting:
10 bits
A typical basis connection is reported in the figure 5.5.1.1.
The assignment of the Analog Inputs for a specific function, is described in the figure 7.5.1 at the menu
FREQ
and
RAMPS.
I.200 An In 1 type
(Analog Input 1 type)
Setting of the Analog Input 1, in accordance with the type of reference control, available on its HW.
I.200 = 1 Un10V o 0-20mA
I.200 = 2 4-20mA