Autoreset Configuration
The Autoreset function allows the automatic restoring of the working of the drive, after the detection of some alarms.
It will be active only with an appropriate setting of the following parameters and if these alarms have been caused by :
undervoltage
(UV)
overvoltage
(OV)
overcurrent
(OC)
overcurrent desat
(OCH)
external fault (programmable)
(EF)
serial time out
(St)
P.380 Autoreset attmps
(Autoreset attemps)
Setting of the maximum number of attempts for the restarting, after the detection of the alarms.
P.381 Autoreset clear
When enabled, it clears the number of events setted with
Autoreset attmps (P.380)
parameter, if for 10 minutes
no alarm has been detected.
P.382 Autoreset delay
Delay that elapses between the failure detection and the beginning of the autoreset sequence.
P.383 Autores flt rly
(Autoreset fault relay)
Definition of the status for the relays and digital outputs, during the autoreset function, when programmed as
follows:
Parameters
P.383
Drive OK
Alarm state
No alarm state
0
ON
OFF
ON
1
OFF
ON
OFF
tgy0340
"Relays & Dig Out" programming
N
OTE
!
a normal "Reset" can be enabled also through the digital inputs (see chapter
INTERFACE
, section
Digital inputs
). The reset command will be executed only if the drive is blocked (no RUN or Reverse
commands) and the cause of the alarm has been eliminated.
Code
Name
[Code] & Function.
Default
MIN
MAX
Unit
Variation
IPA
P.380
Autoreset attmps
0
0
255
466
P.381
Autoreset clear
10
0
250
min
467
P.382
Autoreset delay
5
0.1
50
sec
0.1
468
P.383
Autores flt rly
[0] OFF
1
0
1
469
[1] ON
External Fault Configuration
P.400 Ext fault mode
(External fault mode)
Configuration of signalling for the "
External fault alarm
".
As per factory setting the function is programmed on the digital input 6 (terminal 6).
P.400 = 0
Always signalled
- Autoreset not possible
P.400 = 1
Signalling only when applied the RUN command
- Autoreset not possible
P.400 = 2
Always signalled
- Autoreset possible
P.400 = 3
Signalling only when applied the RUN command
- Autoreset possible