120 Chapter 7 - Parameters Description
User Manual
7.8 Menu C - COMMANDS
All the parameters of the COMMAND menu require to be executed according to the procedure listed below.
Save parameters command is used as example.
COMMAND
C000
Save parameters
E
Save parameters
Confirm?
NO
E
Save parameters
Run
Save parameters
Done
COMMAND
C000
Save parameters
Save parameters
Confirm?
YES
Basic
C.000 Save parameters
Every changing of each parameter, is immediately accepted and executed by the drive.
However, permanent storage of them, is performed only by the execution of this command.
Unsaved modifications to any parameter will be lost when the drive is turned off.
C.001 Recall param
The function recalls the parameters that were previously stored, replacing the ones currently in use.
C.002 Load Deafult
Recall of the factory parameters.
The storage of them is a choice of the user.
Alarm Register Reset
C.020 Alarm clear
The function reset completely the
Alarm List
register (
D.800 D.803
).
External Key
C.040 Recall key prog
Recalling and storage of the parameters contained in the optional external key
QUIX-PRG.
The key has to be set in the connector JP10 on the regulation board.
C.041 Save pars to key
Storage of the inverter parameter on the optional external key
QUIX-PRG.