User Manual
Chapter 3 - Description, Components and Specifications 17
Disposing of the drive
DVS drives must be disposed of as electronic waste in compliance with national legislation.
The front covers are made from recyclable ABS.
3.3.2. Mains input and drive output connections
DVS drives must be connected to a mains supply capable of providing symmetrical short circuit power better than or equal
to the values given in table 3.3.2.1. See section 5.7.1 for information on the addition of mains chokes.
See table 3.3.2.1 for the permitted mains voltages. Cyclical phase direction is irrelevant. Voltages below the minimum
tolerance threshold cause the drive to lock.
The drive can be restarted automatically after an alarm condition occurs (see section 6.15 for further details on this function).
N
OTA
!
Under certain circumstances it may be essential to add mains chokes and EMI filters to the drive input.
Refer to the Chokes and filters section.
DVS drives and mains input filters have earth leakage currents greater than 3.5 mA. EN 50178 standard requires that in the
presence of earth leakage currents greater than 3.5 mA, the ground connection (to the PE terminal) must be fixed.