68 Chapter 7 - Parameters Description
User Manual
7.4 Menu I - INTERFACE
Digital Inputs Regulation Board
I.000 Dig input 1 cfg
(Digital input 1 configuration)
I.001 Dig input 2 cfg
(Digital input 2 configuration)
I.002 Dig input 3 cfg
(Digital input 3 configuration)
I.003 Dig input 4 cfg
(Digital input 4 configuration)
I.004
Dig input 5 cfg
(Digital input 5 configuration)
Not used
The regulation board provides as standard 8 opto-coupled digital inputs. A PNP or NPN logic level, can be selected according
to figure 5.5.1. Every input is programmable with a specific code and function, as shown in the list below.
DIGITAL INPUTS SELECTION LIST
:
Code
LCD display
Description
0
None
Not active
1
Run
RUN command for the motor START
2
Reverse
Speed REVERSE command
3
Ext Fault NO
External fault with NO (Normal Open) contact
4
Ext Fault NC
External fault with NC (Norm. Closed) contact
5
Alarm reset
Alarm reset command
6
Jog
JOG frequency reference enabling
7
Freq sel 1
Binary selection for Multispeed
8
Freq sel 2
Binary selection for Multispeed
9
Freq sel 3
Binary selection for Multispeed
10
Freq sel 4
Binary selection for Multispeed
11
Ramp sel 1
Binary selection for Multiramp
12
Ramp sel 2
Binary selection for Multiramp
13
Enable NO
Drive Enable with NC (Norm. Closed) contact
14
Enable NC
Drive Enable with NO (Normal Open) contact
15
DCBrake en
Enabling of the DC braking function
16
DCBrake
Command for execution of DC braking
17
Autocapture
Execution of the flying restart
18
Ramp enable
Enabling / Disabling of the Ramp block
19
Zero ref
Ramp to 0Hz & main commands active
20
PID enable
Enabling of the PID regulation
21
PID freeze
Enabling PID freeze output signal.
22
PID gain sel
Initilizing of the Integral value of PID
23
Motorpot Up
Motorpotentiometer reference increasing
24
Motorpot Dn
Motorpotentiometer reference decreasing
25
Reset Motorp
Reset of Motorpotentiometer reference
26
Fast stop
Emergency stop (with Dec time 3 delay)
27
Zero freq
Enabling output freq. to zero.
Code
Name
[Code] & Function
Default
MIN
MAX
Unit
Variation
IPA
I.000
Dig input 1 cfg
See Digital inputs selection list
7
0
27
100
I.001
Dig input 2 cfg
As for I.000
8
0
27
101
I.002
Dig input 3 cfg
As for I.000
9
0
27
102
I.003
Dig input 4 cfg
As for I.000
6
0
27
103