62 Chapter 7 - Parameters Description
User Manual
7.3 Menu S - START-UP
N
OTE
!
The
START UP
menu is a set of parameters and functions that allow a quick start of the motor.These
parameters are duplicated in other menus of the drive, Therefore, their modification can be performed
in any of the menus where the parametes are present.
Power Supply
S.000 Mains voltage
Rated value of the main voltage [V].
The undervoltage trip function is based on this value (see chapter
PARAMETER
, section
Undervoltage
configuration
).
S.001 Mains frequency
Rated value of the line voltage frequency [Hz].
Code
Name
[Code] & Function
Default
MIN
MAX
Unit
Variation
IPA
S.000
Mains voltage
110
230
110
240
V
404
220
230
240
S.001
Mains frequency
50
(****)
50
60
Hz
405
60
(****) parameter value dependent on drive type.
V/F Ratio
S.100 Max out voltage
(Maximun output voltage)
Maximum value of the voltage applied to the motor (normally set as the nameplate, see figure 7.3.2).
S.101 Base frequency
Rated frequency of the motor (given on the nameplate, see figure 7.3.2)
It means the working frequency of the drive, at which the
Max out voltage
is associated
(S.100).
S.100
(S.101)
(S.201)
F
(n)
V
S.100
S.101
S.201
F
(n)
V
Figure 7.3.1: V/F Ratio
N
OTE
!
For further setting of the V/F ratio, see the chapter
PARAMETER
, section
V/F Curve