![TBEA TC500K3US-O Скачать руководство пользователя страница 63](http://html1.mh-extra.com/html/tbea/tc500k3us-o/tc500k3us-o_installation-manual_823554063.webp)
TC500K3US-O Installation Instructions
57
Table 8-2 Comparison table of connection cables
Cables
Connection
bore diameter
Wire diameter
requirements
(mm²
)
Torque
(
in-lbs)
Wire diameter
requirements
(ANSI)
PV array DC +
Φ11
67.4
196
(22N·m)
2/0 AWG
PV array DC-
Φ11
67.4
196
(22N·m)
2/0AWG
Grounding cable -
power cabinet
Φ13
85
346
(39N·m)
3/0 AWG
Grounding cable -
AC side
Φ13
85
346
(39N·m)
3/0 AWG
Grounding cable -
DC side
Φ13
85
346
(39N·m)
3/0 AWG
Communication
lines
Φ5
0.75
27 (3N·m)
17AWG
L1 phase grid
Φ18
6×253
1064
(120N·m)
500Kcmil×6
L2 phase grid
Φ18
6×253
1064
(120N·m)
500Kcmil×6
L3 phase grid
Φ18
6×253
1064
(120N·m)
500Kcmil×6