TC500K3US-O Installation Instructions
34
Reliable electrical connections between cable trenches as well as cable
trenches and ground electrodes are required.
Section of cable trenches is shown in Figure 5-6, the user can determine
the number of cable brackets according to the requirements, and the
communication, control and power cables shall be separated when laying the
cables, and DC circuits and AC circuits shall be laid separately. In this way, the
installation and maintenance will be easier, and interference of power circuits
to communication and control signal lines will be reduced.
Figure 5-6 Sectional view of cable trenches
5.3.2 Ventilation Requirements
A lot of heat will be generated when TC500K3US-O is running, so the
electrical performance of the equipment will be affected when its temperature