TC500K3US-O Installation Instructions
56
The DC input and AC output circuits are isolated from the enclosure. The
PV system grounding shall be installed per the requirements of section 690.41
through 690.47 of national electrical code, ANSI/NFPA 70, PV system
grounding installation is the responsibility of the installer.
8.3 Cable Requirements
Requirements for selecting the cable are as follows:
AWG 90
℃
copper is recommended to use.
The current is proposed to be not greater than 3A through 1mm²
wire.
The wires of same sizes and types shall be selected for the same side of
the cable.
The diameter of the single wire is avoided to be too large.
Cables shall be crimped with wire terminals with UL certification, and the
sizes of wire terminals shall be according to the actual installation situations.
The maximum current of DC side of the inverter is 1600A, and the
maximum current of AC side is 1443A. The recommended specifications of
connection cable are shown in Table 8-2.