TC500K3US-O Installation Instructions
29
Figure 5-1 Requirements of ground for TC500K3US-O installation
5.2.2 Requirements of the Minimum Space for Outdoor Uses
The inverter and the surrounding objects must have the minimum distance
when installing the inverter, to meet the requirements in maintenance, escape
and ventilation. The escape routes must meet the American minimum
requirements of 915mm in order to satisfy the minimum requirements for a
single person to go through freely, and also, enough spatial distance will
provide good conditions for the equipment and cables to release the heat,
avoiding the shutdown and even fire and other dangerous situations caused by
overheating.
Minimum installation space for single TC500K3US-O
The space of 1800mm shall be provided in front and over 1800mm
(32inch) to the back, and over 600mm (24inch) to the top for easy installation,