TC500K3US-O Installation Instructions
55
The inverter can be connected to the grid only when the local power
company permits.
Electrical installation must comply with local electrical installation
standards.
Only
qualified
electricians
or
personnel with
professional
qualification can carry out the electrical installation of the product.
8.2 Input and Output Requirements
PV array
The open circuit voltage of PV array shall not exceed 600Vdc; otherwise
the inverter may be damaged. The maximum power of PV array of
TC500K3US-O can be configured to 500kW.
Public grid
TC500K3US-O will continue to detect whether the power grid meet
grid-connected conditions. To meet the grid limits of grid-connected conditions,
the three-phase power grid is used. Meanwhile, the grid-connected inverter is
installed after getting the permission of the local power sector.
Table 8-1 Grid requirements
Parameter name
Parameter requirements
Grid voltage(Vac)
176~220
Grid frequency(Hz)
59.8~60.5