TC500K3US-O Installation Instructions
30
cooling, maintenance and enough space to escape in emergency.
Details are shown in Figure 5-2:
Figure 5-2 Requirements of installation space for a single set of TC500K3US-O
Items
Recommended minimum
distance (mm)
Description
A
1700(70inch)
Minimum distance in front meeting the
normal opening and closing of the front door,
user operations, safe evacuation and other
requirements
B
1300(52inch)
Minimum distance rear
C
600(24inch)
Minimum distance above
D
600(24inch)
Minimum distance at right side, 600mm
(24inch) is the distance from the closed wall
E
600(24inch)
Minimum distance at left side
The minimum space of installation space for two TC500K3US-O.
First way: back to back