20.2.4. VERIFICATION OF COMMUNICATION WITH THE COMMUNICATING AMBIENCE TERMINAL
By default, the ambience terminal is declared in the regulator. This means that
an alarm will be visible on the screen of the
Aqu@ Scop HT
a few seconds
after the power supply is switched on, if the terminal is not connected. Proper
terminal operation can be checked on screens
TH1
to
TH3
.
All the terminal parameters are accessible via the "
Ambience Terminal
" menu
in the main menu (key
).
Screens: TH0 to TH3.
20.2.5. COMPRESSOR SUMP HEATER FUNCTION ACTIVATION
After the first power ON (compressors OFF),
and for any outdoor air temperature
, manually switch ON the
compressor sump heaters.
Before starting the compressors, the sump heaters must be powered On for at
least 2 hours in order to evaporate any liquid refrigerant that could be in the
compressors to ensure their lubrification at the first start-up.
The screen
TH0
appears when the terminal is deactivated (installation menu)
or disconnected. This screen provides access to a set temperature to facilitate
the inputting of water law offset values.
20.2.6. TIME AND DATE VERIFICATION
The time and the date are used to manage the:
²
Alarm log.
²
The DHW Legionnaires Disease protection function.
When a communicating ambience terminal is connected to the
Aqu@ Scop HT
, the time is automatically
updated in the regulator. The date is managed solely by the regulator. At commissioning, check:
²
The date, screen
P4
. Update as required in the "
Config installation
" CI5
menu.
²
The time (screen
P4
) if no ambient terminal is connected. Update as
required in the "
Config installation
" CI5 menu.
Содержание AquaScop HT V2
Страница 1: ...Air water Heat Pump Installation and maintenance manual 12 0 â 17 9kW 12 6 18 9 Aqu Scop HT V2 ...
Страница 2: ......
Страница 57: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO ...
Страница 79: ...XXIII Aqu Scop HT V2 APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO ...
Страница 80: ...XXIV Aqu Scop HT V2 APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO ...
Страница 81: ......
Страница 82: ......
Страница 83: ......