Press the
key twice to move the cursor to the
GENERAL OFF
parameter.
Use the
/
arrows to change this parameter to
ON
.
Press
to validate and then on the key
.
.
From the main menu, use the
/
arrows to highlight the "
ON/OFF-
SUMMER/WINTER
" menu. Validate this selection by pressing the
key. The
display moves to the
O0
screen.
In order to start, the
Aqu@ Scop HT
must always be
ON
at the level of the appliance's display. In addition, the
ambience terminal must be in demand mode (when it is connected). To force the terminal to enter demand
mode, change it to Comfort mode
with an ambience temperature set at 30° C.
The appliance
OFF
function will always have priority and therefore you will never be able to start the
Aqu@ Scop HT
in this mode.
If the ambience terminal is in demand mode, and if no alarm is active and the water temperature condition
permits (inlet water
at least 7° C below set temperature
), the
Aqu@ Scop HT
will start operating.
Normal
Aqu@ Scop HT
operation is guaranteed with an appliance inlet (system return) water temperature
above 20° C.
20.2.7. AQU@ SCOP HT ON/OFF SETTINGS
Содержание AquaScop HT V2
Страница 1: ...Air water Heat Pump Installation and maintenance manual 12 0 â 17 9kW 12 6 18 9 Aqu Scop HT V2 ...
Страница 2: ......
Страница 57: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO ...
Страница 79: ...XXIII Aqu Scop HT V2 APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO ...
Страница 80: ...XXIV Aqu Scop HT V2 APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO ...
Страница 81: ......
Страница 82: ......
Страница 83: ......