English
Screen L3
Screen L4
Screen L1
Screen L2
RADIATOR HEAT CURVE PARAMETERS
20
25
30
35
40
45
50
55
60
65
70
-15
-10
-5
0
5
10
15
20
Outdoor temperature (°C)
Leaving water temperature setpoint (°C)
Correction Coef. 0,5
Correction Coef. 0,8
Correction Coef. 1,0
Base outd. T.
Base water SPT
39
Aqu@Scop HT V2
Information screen for the outdoor temperature calculated automatically by
the
Aqu@ Scop HT
. With the preceding default parameters, the value of 5.4°
C means that below an outdoor temperature of 5.4° C the
Aqu@ Scop HT
will
start the large compressor or the two-stage compressor. Above 5.4° C the
Aqu@ Scop HT
will start the small compressor.
The value of the outdoor balance temperature displayed on
L4
is the one
updated by the
Aqu@ Scop HT
after running for some time, in the event that
the
Aqu@ Scop HT
detects a lack of capacity with the small compressor.
Zero reset
: This is required in the event of changes to the heat curve parameters
in order for the
Aqu@ Scop HT
to register these changes. The parameter on
screen
L3
is then recopied into screen
L4
.
Altitude
: Installation site altitude, in km (e.g. 0.5km equals 500m. Default
setting: 0).
Base outd. T.
: Typical outdoor temperature for the installation region (Default
setting: -7°C).
Corr. Coef.
: Correction Coefficient for the base of the slope. This is a simple
way of changing the water set temperature (Default setting: 0.8).
20.2.3. HEAT CURVE PARAMETERS
On the main menu (key
), use the
/
arrows to highlight the "
HEAT CURVE
" menu. Validate this
selection with the
key. This moves the display to the
L1
screen. Use the
and
/
keys to set
the following parameters:
Losses at base Outdoor Temp
: Estimated heat loss for the dwelling for an
ambient temperature of 20°C and a base outdoor temperature (e.g. -7°C).
This parameter is used to calculate the outdoor temperature that triggers
the change from small compressor mode to two-stage compressor mode.
This value is capped at the maximum capacity of the
Aqu@ Scop HT
model in
question for this same outdoor temperature (Default value = Maximum value).
Water outlet temperature at -07°C Outdoor temperature
: Outlet water
temperature required at the base outdoor temperature (-7°C for example) to have an ambient temperature
of 20°C (Default setting: 65°C).
Содержание AquaScop HT V2
Страница 1: ...Air water Heat Pump Installation and maintenance manual 12 0 â 17 9kW 12 6 18 9 Aqu Scop HT V2 ...
Страница 2: ......
Страница 57: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO ...
Страница 79: ...XXIII Aqu Scop HT V2 APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO ...
Страница 80: ...XXIV Aqu Scop HT V2 APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO ...
Страница 81: ......
Страница 82: ......
Страница 83: ......