14.2. PROGRESSIVE START-UP
The
Aqu@ Scop HT
18-9 is equipped with a progressive starter
(soft start) for the C1 compressor. The starter is situated in the
electrical box of the outdoor unit and marked "
AS1
".
It is important to check the following settings:
²
Start slope
1s
²
Stop slope
0s
²
Minimum starting voltage
60%
Start slope
Stop slope
Minimum
starting
voltage
3N~400V-50HZ
IMPORTANT :
The compressors are equipped with a soft starter. The starter is situated in the electrical box of the outdoor
unit and marked "
AS1/2
".
230V +/-10% 50Hz
THE LED’s INDICATE THE FOLLOWING CONDITIONS:
Green
diode
Red diode Meaning
Recommended action
Comments
On
Off
No fault
Off
Off
No supply voltage present
at starter terminals.
Check the power supply to the PAC.
Check the condition of the 230V
protection fuse. Replace the fuse if it
has melted.
Flashing
Off
Insufficient supply voltage
(compressor stopped).
Measure the compressor starter
supply voltage at rest. Cut the power
supply to the PAC and check whether
or not the fault reappears. Refer to
the following cause in the event of
repeated failure.
Defective starter power
supply component.
Cut the power supply to the PAC. If the
fault persists, replace the starter.
On
Flashing
twice
Insufficient compressor
starting voltage (<190V).
Check the mains supply voltage at
rest. Contact the electricity supplier if
< 207V.
The alarm resets itself automatically
after 5 min. If the fault re-occurs
during the next start-up procedure,
the compressor seizes and the power
supply has to be disconnected to reset
it.
With the compressor running, check
the mains supply voltage and the
starter output voltage. In the event of
major voltage drop, check the diameter
of the PAC power supply cable. As
a last resort, contact the electricity
supplier.
On
Flashing 3
times
Excessive compressor
starting current.
Force the compressor to start several
times and check whether it is a one-
off or recurring fault.
The alarm resets itself automatically
after 5 min. If the fault re-occurs
during the next start-up procedure,
the compressor seizes and the power
supply has to be disconnected to reset
it.
If the fault persists, when the
compressor is running, check for
normal current draw. In the event of
excessively-high current draw, replace
the compressor.
Starter fault. Replace the starter.
On
Flashing 4
times
Starter internal condenser Replace the starter.
On
Flashing 5
times
Incomplete or defective
compressor starting
sequence
Force the compressor to start several
times and check whether it is a one-
off or recurring fault.
The alarm resets itself automatically
after 5 min. If the fault re-occurs
during the next start-up procedure,
the compressor seizes and the power
supply has to be disconnected to reset
it.
In the event of a persistent fault, check
the compressor power supply cable.
Содержание AquaScop HT V2
Страница 1: ...Air water Heat Pump Installation and maintenance manual 12 0 â 17 9kW 12 6 18 9 Aqu Scop HT V2 ...
Страница 2: ......
Страница 57: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO ...
Страница 79: ...XXIII Aqu Scop HT V2 APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO ...
Страница 80: ...XXIV Aqu Scop HT V2 APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO ...
Страница 81: ......
Страница 82: ......
Страница 83: ......