Sutron Corporation X-Link Operations & Maintenance Manual, Rev 1.63 5/24/2016 pg. 172
18.2.1.7.
Modbus Baud Rate
Default is 9600 baud. Available communication speeds are
9600
19200
28800
38400
Note: Care must be taken to make sure the selected speed matches that of the
master or there will be communication problems.
18.2.1.8.
Modbus Parity
Default is Even. Available choices include Even, Odd and None.
Note: Care must be taken to make sure the selected parity matches that of the
master or there will be communication problems.
18.2.1.9.
Modbus Delay before Tx
Default is 100ms. This identifies the number of milliseconds to wait before
starting data transmission. This is useful if the device is connected to a radio
requires keying initialization before data transmission. The possible delay ranges
are 10ms – 2000ms.
18.2.1.10.
Modbus Delay after Tx
Default is 10ms. This identifies the number of milliseconds to wait after data
transmission. This is useful if the device is connected to a radio that requires a
hold-off time after data transmission has completed. The possible delay ranges
are 10ms – 2000ms.
18.3.
Modbus Function Codes
The following table identifies the functions that are supported. Each diagnostic
counter is cleared when the device is powered up or reset.
Code
Hex
Subcode
Hex
Read Holding Registers
0x03
Read Input Register
0x04
Write Single Register
0x06
Diagnostic
0x08
Return Query Data
0x00
Diagnostic
0x08
Clear Counters
0x0A
Diagnostic
0x08
Return Bus Message Count
0x0B
Diagnostic
0x08
Return Bus Comm Error
0x0C
Diagnostic
0x08
Return Bus Exception Count
0x0D
Diagnostic
0x08
Return Slave Message Count
0x0E
Diagnostic
0x08
Return Slave Broadcast Count
0x0F
Diagnostic
0x08
Return Bus Char Overrun Count
0x12
Write Multiple Registers
0x10
Sutron Function Code
0x41
Get Log
GL